Baoding dry type transformer is composed of primary winding, secondary winding and iron core.
Transformer factory
Due to the characteristics of the core itself and only participate in the transformer's magnetic-electrical and electric-magnetic energy replacement, so generally not damaged.
And winding is copper (or aluminum) conductor with insulation layer layer wound, work by the voltage, current, easy to produce open circuit, inter-turn short circuit fault, so detection transformer is mainly to check the performance of its winding.
General personnel, in the absence of professional instruments, can use the following methods to detect the transformer is good or bad:
1, with the resistance of the multimeter to check the winding on and off, eliminate the open circuit fault.
If each winding is a path, the conductor in the winding can be basically judged to be on.
2, the input low voltage method, simple to eliminate the winding short circuit fault.
Find an ac low-voltage (6V or 12V) isolating transformer and a 1A fuse (depending on the power size of the transformer to be tested, select the current value of the fuse), connect the output voltage of the isolating transformer through the fuse to the input windings of the transformer to be tested, and then connect the power supply.
A, if the insurance immediately burned down, it can be concluded that the transformer winding internal short circuit fault ---- -- damage, can not be used.
B. if the insurance is normal, wait for 10 minutes and observe the temperature rise of the transformer. The temperature rises quickly and it feels very hot to the hand. It can be judged that the primary winding may have inter-turn short-circuit phenomenon ---- -damaged and cannot be used.
C, if the insurance is normal, the temperature rise is not big, the no-load voltage of the secondary winding can be measured. The measured value does not conform to the transformer ratio, indicating that the secondary windings may be damaged and cannot be used.
D, if the insurance is normal, the temperature rise is not big, measure the no-load voltage value of the secondary winding in line with the transformer ratio, that the secondary winding is good ---- -- can be used.
The rated voltage and rated load can be applied on the baoding dry type transformer only after passing all the above tests, so as to check the working status of the baoding dry type transformer.
Baoding zhongyi electric material manufacturing co., LTD. Is a professional transformer manufacturer in baoding transformer factory. It has professional production equipment, lifting equipment, tooling and testing equipment.
Main products: baoding dry type transformer, baoding box type transformer, baoding oil immersed transformer, baoding high and low voltage complete sets of equipment, etc. I companies to follow "detail decides success or failure, honesty molded the future" of the enterprise purpose, adhere to "quality measuring market, seek development by innovation, to management for efficiency" business philosophy, to make my company's products are widely used in power plant, chemical, construction, mining, metallurgy, rail transportation and other industries, to meet the needs of various users, my company rely on superior product quality, thoughtful service, won the trust of our customers.