Baoding oil-immersed transformer due to containing transformer oil, easy to burn, and baoding oil-immersed transformer is a kind of power equipment, its security is related to the normal operation of the whole power system, therefore, the fire prevention to baoding oil-immersed transformer must be well done, it is related to the whole power system for safety. To this end, baoding oil transformer supplier gives several fire prevention Suggestions, so that you can make a reference.
The manufacturer of baoding oil-immersed transformer said that the oil-immersed transformer should pay special attention to the following fire safety measures:
1. When the oil content of the oil immersed transformer and other oil-filled electrical equipment is above 1000Kg, the oil storage pit and the public collecting tank shall be set up, and the transformer pebble-stones shall be placed in reserve for fire prevention and unloading.
2. When the distance between the outer wall of the plant and outside oil immersed transformer is less than the specification table, the outer wall shall adopt a firewall. The distance between the wall and the outer edge of the transformer should not be less than 0.8m.
3. Oil-immersed transformers with more than a certain amount of oil have certain fire spacing. For example, oil-immersed transformers with oil content of more than 2500kg should be between 600kg and 2500kg of oil-filled electrical equipment, and the fire spacing should not be less than 5m.
4. When the fire spacing between two adjacent baoding oil-immersed transformers does not meet the requirements, the fire partition wall or the top of the firewall shall be set up. The single phase baoding oil transformer can only set fire partition wall or fire curtain.
5. When the outer edge of the outer edge of the outer wall of the factory is less than 5m, it should not open doors and Windows or holes in the range of the total thickness of the transformer and 3m on both sides of the transformer. The fire resistance limit shall not be lower than 0.9h for doors and fixed Windows on the firewall outside its range.
6. The baoding oil immersed transformer should be set up with fixed water spray and other fire extinguishing system according to the existing regulations. Oil-immersed plant transformer should be set in a separate room, the door of the room should be the class b fire door open to the outside, and straight out of the house or corridor, should not open to other rooms.
Baoding oil-immersed transformer suppliers said the oil-immersed transformer fire prevention work should not be ignored, is the necessary condition to ensure the normal operation of baoding oil-immersed transformer, but also to ensure the safety of the whole power system running strong. Therefore, for the above introduction of the baoding oil transformer fire prevention measures, I hope that you can reference and reference.
Billion in baoding electric materials co., LTD is specialized in the production of transformer baoding transformer factory manufacturers, with professional production equipment, hoisting, tooling and testing equipment, established a perfect quality management system, product performance indicators have reached the standard.
Company's main products: baoding dry type transformer, baoding box transformer, baoding oil immersed transformer, baoding high and low voltage complete equipment. I companies to follow "detail decides success or failure, honesty molded the future" of the enterprise purpose, adhere to "quality measuring market, seek development by innovation, to management for efficiency" business philosophy, to make my company's products are widely used in power plant, chemical, construction, mining, metallurgy, rail transportation and other industries, to meet the needs of various users, my company rely on superior product quality, thoughtful service, won the trust of our customers.